XECO Power Optimization · Patent US 12,375,324 B2

Optimize the infrastructure you already have.

Improve power quality and put unused electrical capacity to work at existing data centers and colocation facilities. Our patented XECO technology, installed as ECBS (Energy Current Balancing System) units, removes harmonic and reactive current in real time.

01The Technology

Active power filters, circuit by circuit.

ECBS is a set of devices that work together to clean up power across a site. Each one has a job:

Devices are placed near the loads, circuit by circuit, so correction holds as AI workloads swing.

Active power filters (APFs)

Measure each circuit's current and inject an equal and opposite current, canceling harmonics and reactive power in real time.

Line conditioners

Absorb lower-order harmonics and high-frequency noise close to the load.

Return units

Keep filtered harmonic current from recirculating through the neutral.

Monitoring

Meters at the main switchgear and on every filter, feeding your building management system.

Before ECBS · distorted current After ECBS · clean 60 Hz
Before ECBS: distorted current

ECBS raises power factor to > 0.98. The result: less current for the same IT load, cooler equipment, more headroom and stable voltage on utility, generator or UPS.

ECBS unit

Installation

Installed across the distribution network.

ECBS units connect in parallel at spare breakers on panels, switchgear or fuse disconnects, covering the main circuits. Installation scope and any outage requirements are confirmed during site engineering.

02Live Monitoring

See your capacity, live.

Revenue-grade metering shows what's connected, what's in use and what ECBS has recovered.

XECO monitoring portal showing connected, in-use, available and recovered capacity

03How ECBS Works

Recover usable electrical capacity.

The problem

Distorted current eats headroom.

Transformers are sized with margin, and harmonic and reactive current eat into what's left. Mixed loads such as VFDs, UPS systems and legacy IT draw distorted current that heats windings and forces derating.

ECBS

Filtered in real time.

Patented ECBS units correct harmonic and reactive current in real time, responding in under 100μs.

The result

Headroom, given back.

ECBS raises power factor to > 0.98, reducing the apparent power (kVA) needed for the same IT load. That can free up capacity for compute or other loads. Results are site-specific.

<5%THDi after ECBS
Raises power factor to > 0.98Without capacitor banks
<100μsResponse time

04Case Study

Measured at an operating colocation facility.

A multi-tenant colocation facility with more than 10 MW of demand, double-conversion UPS and transformers already designed for harmonic loads.

0.986 POWER FACTOR, AFTER 0.60 1.00
Before 0.810After 0.986

The challenge

  • Power quality concerns after utility events that affected cooling
  • Harmonic loading from server power supplies
  • Poor power factor at the utility service entrances

What we did

  • Engineering review and a baseline metering campaign
  • ECBS devices on the main bus and cooling circuits, and active power filters on the IT distribution
  • Installed by the operator's own electrical contractor; commissioned and tuned by XCT
  • Results verified against the baseline
  • 0.810 → 0.986 power factor
  • 16% → 6% harmonic distortion
  • 57 → 43 °C switchgear temperature
  • ~18% less kVA for the same load

Measured on site. Results vary by site.